3-Gang plate with mortise cylinder bracket and card
reader Model No. LDA9608/9618 Overview The LDA 9608/9618 Local Door Alarm has field ready mounting for an industry standard proximity mullion type card reader. The LDA 9608/9618 monitors door contacts, motion sensors, and access control devices to determine and annunciate the status of a controlled door. A sounder alerts area personnel of a door control violation, and the building alarm system is notified with alarm relay contacts. The Warning Alarm feature reduces nuisance alarms by sounding a local alarm a few seconds before a Door Held Alarm. An integrated card reader mounted on the plate allows for a very clean and tidy final installation. |
|
![]() Available with or without Card Reader LDA9608/9618 Without Card Reader LDA9608R/9618R With Card Reader |
Standard Features
|
|
The LDA was developed with the intention of reducing
nuisance alarms caused by improper door usage, as well as providing
flexible door alarm monitoring. Several field selectable operating modes
allow system integrators to utilize a single type of door alarm to
handle a large variety of alarm applications. Technical Specifications |
|
| Power | 12 - 24 VAC/VDC @ 250 ma. max. |
| Inputs | 1 Normally Closed fully supervised door input. (1 Kohm =
closed, 2 Kohm = open, else = supervision fault). Supervision monitoring may be disabled at installation. 3 Access Control inputs: Remote N/O alarm bypass, N/O or N/C request to exit shunt, and fail-safe or fail secure lock voltage monitoring (12 - 24 VAC/VDC). |
| Outputs | 1 Normally Closed Alarm Relay rated @ 1/2 A. Opens with forced door alarm or door held alarm. 1 Normally Closed Door Status Relay rated @ 1/2 A follows the door contact. after request to exit shunt. Alarm sounder @ 85 dB (9604) or 105 dB (9614). Pulsing tones indicate warning alarm, and constant tone indicates door violation alarm. Green LED indicates access mode, Red indicates armed. |
| Time Delays |
Access delay - adj. 0 - 60 sec. Shunts the alarm function
for the duration of the delay Warning delay - adj. 0 - 60 sec. Sets the duration of the warning alarm. Alarm automatic reset delay - adj. 0 - 60 sec. Sets the duration of an alarm if the automatic reset feature is enabled. |
| Field Options | Forced door alarm disable. Supervision monitoring disable. N/O or N/C request to exit monitoring. Fail-safe or fail secure lock voltage monitoring. Alarm automatic reset disable. |
| Card Reader | Mullion Mount Mini Proxy Reader |
| Mounting | 2 Gang, 2-½ inch deep electrical box. |
| Terminal Strips | Fixed Terminal strips accept up to 16 AWG wires. |
| Card Reader Compatability |
Supports Industry standard mini card reader and mullion mount reader. |
![]() ![]() |