Double Gang Door Alarm With Card Reader Model No. LDA9607/9617 Overview The Local Door Alarm with integrated industry standard proximity and/or smart card (wiegant output) reader (LDA) monitors door contacts, motion sensors, and access control devices such as card reader systems or keypads to determine and annunciate the status of a controlled door. A sounder alerts area personnel of a door control violation, and the building alarm system is notified with alarm relay contacts. The Warning Alarm feature reduces nuisance alarms by sounding a local alarm a few seconds before a Door Held Alarm. An integrated card Reader mounted on the plate allows for a very clean and tidy final installation. |
|
Card Reader not inlcuded |
Standard Features
|
|
The LDA was developed with the intention of reducing
nuisance alarms caused by improper door usage, as well as providing
flexible door alarm monitoring. Several field selectable operating modes
allow system integrators to utilize a single type of door alarm to
handle a large variety of alarm applications. Technical Specifications |
|
| Power | 12 VDC @ 500 ma. max. |
| Inputs | 1 Normally Closed fully supervised door input. (1 Kohm =
closed, 2 Kohm = open, else = supervision fault). Supervision monitoring may be disabled at installation. 3 Access Control inputs: Remote N/O alarm bypass, N/O or N/C request to exit shunt, and fail-safe or fail secure lock voltage monitoring (12 - 24 VAC/VDC). |
| Outputs | 1 Normally Closed Alarm Relay rated @ 1/2 A. Opens with forced door alarm or door held alarm. 1 Normally Closed Door Status Relay rated @ 1/2 A. Follows the door contact. Alarm sounder @ 85 dB (9602) or 95 db (9612). Pulsing tones indicate warning alarm, and constant tone indicates door violation alarm. Green LED indicates access mode, Red indicates armed. |
| Time Delays |
Access delay - adj. 0 - 60 sec. Shunts the alarm function
for the duration of the delay Warning delay - adj. 0 - 60 sec. Sets the duration of the warning alarm. Alarm automatic reset delay - adj. 0 - 60 sec. Sets the duration of an alarm if the automatic reset feature is enabled. |
| Field Options | Forced door alarm disable. Supervision monitoring disable. N/O or N/C request to exit monitoring. Fail-safe or fail secure lock voltage monitoring. Alarm automatic reset disable. |
| Card Reader | Mullion Mount Mini Prox Reader |
| Mounting | 2 Gang, 2-½ inch deep electrical box. |
| Terminal Strips | Fixed Terminal strips accept up to 16 AWG wires. |
| Card Reader Compatability |
Supports Industry standard mini card reader and mullion mount reader. |
![]() ![]() |