Double Gang Door Alarm w/ Keypad Model No. LDA9606/9616 Overview The Local Door Alarm (LDA) monitors door contacts, motion sensors, and access control devices such as card reader systems or keypads to determine and annunciate the status of a controlled door. A sounder alerts area personnel of a door control violation, and the building alarm system is notified with alarm relay contacts. The Warning Alarm feature reduces nuisance alarms by sounding a local alarm a few seconds before a Door Held Alarm. |
|
|
Standard Features
|
|
The programmable keypad allows for users to be added/deleted, codes to be changed, and for codes 3-6 characters in length to be used. Codes and all programming are stored in non-volatile memory and will not be lost when power is removed. Technical Specifications |
|
| Power | 12 VDC @ 500 ma. max. |
| Inputs | 1 Normally Closed fully supervised door input. (1 Kohm
= closed, 2 Kohm = open, else = supervision fault). Supervision monitoring may be disabled at installation. 3 Access Control inputs: Remote N/O alarm bypass, N/O or N/C request to exit shunt, and fail-safe or fail secure lock voltage monitoring (12 - 24 VAC/VDC). |
| Outputs | 1 Normally Closed Entry Alarm
Relay rated @ 1/2 A. Opens with forced door alarm or door held alarm
after lock voltage shunt. 1 Normally Closed Exit Alarm Relay rated @ 1/2 A. Opens with door held alarm after request to exit shunt. Alarm sounder @ 85 dB (9606) or 95 dB (9616). Pulsing tones indicate warning alarm, and constant tone indicates door violation alarm. Green LED indicates access mode; Red indicates armed. |
| Time Delays |
Access delay -
adj. 0 - 60 sec. Shunts the alarm function for the duration of the delay. Warning delay - adj. 0 - 60 sec. Sets the duration of the warning alarm. Alarm automatic reset delay - adj. 0 - 60 sec. Sets the duration of an alarm if the automatic reset feature is enabled. |
| Field Options | Forced door alarm disable. Supervision monitoring disable. N/O or N/C request to exit monitoring. Fail-safe or fail secure lock voltage monitoring. Alarm automatic reset disable. |
| Keypad | 12 key, user programmable keypad, up to 165 codes for operation of any or all functions. Codes can be 3-6 characters in length. |
| Mounting | 2 Gang, 2-½ inch deep electrical box. |
| Terminal Strips | Fixed Terminal strips accept up to 16 AWG wires. |
| Local Door Alarm Operation Options Add the designated suffix to the end of the model number for these operational features. |
|
| BP | Standard Operation as noted on the specification sheet. RE1- N/C Entry Alarm, RE2-N/C Exit Alarm |
| INT | Same operation as noted on the specification sheet except for relay operation. RE-N/C Forced Door Alarm, RE2- Door Held Alarm |
| HS5 | For use at
Card in/ Card Out doors while allowing free exit during emergencies. Lock Voltage Shunt Input resets an alarm. Refer to HS5 Application note. RE1- N/C Forced Door and Door Held Alarm, RE2-N/C Delayed Forced Door Alarm remains closed until 20 seconds after a forced door alarm to allow time to reset alarm prior to transmitting an alarm to the monitoring system. |
![]() ![]() |